Ideally, the best electrical supply would be a constant magnitude and frequency sinusoidal voltage waveform. However, because of the non-zero impedance of the supply system, of the large variety of loads that may be encountered and of other phenomena such as transients and outages, the reality is often different. The Power Quality of a system expresses to which degree a practical supply system resembles the ideal supply system. If the Power Quality of the network is good, then any loads connected to it will run satisfactory and efficiently. Installation running costs and carbon footprint will be minimal. If the Power Quality of the network is bad, then loads connected to it will fail or will have a reduced lifetime, and the efficiency of the electrical installation will reduce. Installation running costs and carbon footprint will be high and/or operation may not be possible at all.
COST OF POOR POWER QUALITY Poor Power Quality can be described as any event related to the electrical network that ultimately results in a financial loss. Possible consequences of poor Power Quality include (Fig. 1): Unexpected power supply failures (breakers tripping, fuses blowing). Equipment failure or malfunctioning Equipment overheating (transformers, motors, …) leading to their lifetime reduction. Damage to sensitive equipment (PC‟s, production line control systems, …). Electronic communication interferences. Increase of system losses. Need to oversize installations to cope with additional electrical stress with consequential increase of installation and running costs and associated higher carbon footprint. Penalties imposed by utilities because the site pollutes the supply network too much. Connection refusal of new sites because the site would pollute the supply network too much. Impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time (flicker) Health issues with and reduced efficiency of personnel,..
The following main contributors to Low Voltage poor Power Quality can be defined: Reactive power, as it loads up the supply system unnecessary, Harmonic pollution, as it causes extra stress on the networks and makes installations run less efficiently, Load imbalance, especially in office building applications, as the unbalanced loads may result in excessive voltage imbalance causing stress on other loads connected to the same network, and leading to an increase of neutral current and neutral to earth voltage build-up, Fast voltage variations leading to flicker. All this phenomena potentially lead to inefficient running of installations, system down time and reduced equipment life and consequently high installation running costs.
In addition to financial loss due to „production stops‟, another factor of the cost of poor Power Quality can be identified by analyzing the extra kWh losses that exist due to the presence of harmonic pollution in typical network components such as transformers, cables and motors. As this loss has to be supplied by the utility power plants, a financial loss and CO2 emissions can be assigned to it. Exact values of this loss depend on the local situation of kWh tariffs and ways that the electrical power is generated (e.g. 3 nuclear power plants have almost no CO2 footprint per kWh generated as opposed to coal power plants for which the footprint is large at around 900-1000 g/kWh produced.
Most harmonic pollution nowadays is created as harmonic current produced by loads in individual installations. This harmonic current, injected into the network impedance transfers into harmonic voltage, (Ohm‟s law); which gets applied to all the loads within that user‟s installation. As a result the user employing harmonic loads may suffer from Power Quality problems. In addition however, the harmonic current produced in one installation if not filtered is also flowing through the feeding transformers into the utility supply and creates harmonic voltage distortion on the public network too. As a result, any utility user connected to the same supply will become affected by the pollution created by another utility customer and could suffer operational consequences in his own installation due to this. In order to limit this type of problems most utilities have adopted Power Quality standards/regulations that shall be respected by the users of the supply network. In extreme cases, non-compliance with these regulations leads to a connection refusal of a new installation, which in turn can have a significant impact on the production and revenue loss of the company. POWER QUALITY PARAMETERS (TERMINOLOGY) Reactive power and power factor (cos In an AC supply, the current is often phase-shifted from the supply voltage. This leads to different power definitions:
The active power P [kW], which is responsible of the useful work, is associated with the portion of the current which is in phase with the voltage. - The reactive power Q [kvar], which sustains the electromagnetic field used to make e.g. a motor operate is an energy exchange (per unit of time) between reactive components of the electrical system (capacitors and reactors). It is associated with the portion of the current which is phase shifted by 90° with the voltage. - The apparent power S [kVA], which gives a geometrical combination of the active and of the reactive powers, can be seen as the total power drawn from the network.
The ratio between the active power and the apparent power if often referred to as the displacement power factor or cos , and gives a measure of how efficient the utilization of the electrical energy is. A cos that equals to 1 refers to the most efficient transfer of useful energy. A cos that equals to 0 refers to the most inefficient way of transferring useful energy. Harmonic distortion The harmonic pollution is often characterized by the Total Harmonic Distortion or THD which is by definition equal to the ratio of the RMS harmonic content to the fundamental.
Voltage unbalance In the symmetrical components theory Fortescue has shown that any three phase system can be expressed as the sum of three symmetrical sets of balanced phasors: the first set having the same phase sequence as the initial system (positive phase sequence), the second set having the inverse phase sequence (negative phase sequence) and the third one consisting of three phasors in phase (zero phase sequence or homopolar components). A normal three phase supply has the three phases of same magnitude but with a phase shifted by 120°. Any deviation (magnitude or phase) of one of the three signals will result in a negative phase sequence component and/or a zero phase sequence component.
Flicker According to the International Electrotechnical Vocabulary (IEV) [4] of the International Electrotechnical Committee (IEC), flicker is defined as 'Impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time'. From a more practical point of view one can say that voltage fluctuations on the supply network cause change of the luminance of lamps, which in turn can create the visual phenomenon called flicker. While a small flicker level may be acceptable, above a certain threshold it becomes annoying to people present in a room where the flicker exists. The degree of annoyance grows very rapidly with the amplitude of the fluctuation. Further on, at certain repetition rates of the voltage fluctuation, even small fluctuation amplitudes can be annoying.
REGULATIONS Utility regulations for harmonic pollution are often based on internationally recognized work undertaken by reputable independent bodies which have defined maximum allowable distortion limits for proper operation of equipment. Commonly quoted examples of such documents targeting harmonic pollution. In general the principle of the regulations is as follows: Limit the total voltage distortion (THDV) contribution that can be created by a customer. In this it is taken into account that if the totally accepted level of voltage distortion is e.g. 5% (of the fundamental voltage), this limit has to be divided over all the users connected. Possibly limits are also imposed for individual harmonic voltage components (e.g. 3% maximum limit for individual harmonic voltages). Convert the voltage distortion limits into current limits which are accepted to flow into the supply system. The current limits can then be easily verified through measurement.
Crazy Nurse Steals The Secret That Big Energy Companies Wanted Buried (SHOCKING)
ReplyDeleteThere are a few simple people that deserve the Medal Of Honor even though they were not in the army... or shared blood on the battle ground.
I'm talking about people like this "CRAZY" nurse who discovered one of the biggest secrets of the mankind... and preferred to share it to community instead of getting millions of dollars for keeping it secret. We're talking about a secret plan that can produce free energy: >> Watch And Cry (Click Here)
It's the same device that was used with great success by the US navy to propel their ships for millions of miles... without any fuel... and that big energy fat cats almost started another war for… just to hide it from the public.
>> Here's The Proof <<
For them it would have meant billions of dollars lost... money that you, I and the rest of the Americans paid for tens of years as electricity bills.
TV’s don't want to talk about it (although they may already know about all the info I'm sharing with you today)... politicians are busy with the North Korea situation... and you're lead to believe that it's normal to pay hundreds of dollars every single month for electricity... when all this time you would have gotten it for free. Here's what is all about: >> The Video That Will Change Your Life <<
Say a prayer, kiss your loved ones because from today you're entering into a new world. A world of free energy. P.S. More than 80,173 people have already watched the video...and I'm receiving tens of emails everyday telling me how they are slashing their power bills... in less than 30 days.
>> Click Here To Find Out What It Is About <<